Select the minimum overcurrent device permitted to protect a branch circuit that serves a 3 phase 208, 8,646 VA electric hot plate, continuous load. The hot plate is served with #8 THWN conductors and all terminal connections are rated for 60 degrees C. Assume the overcurrent device is not approved for 100% continuous load.

Select the minimum overcurrent device permitted to protect a branch circuit that serves a 3 phase 208, 8,646 VA electric hot plate, continuous load. The hot plate is served with #8 THWN conductors and all terminal connections are rated for 60 degrees C. Assume the overcurrent device is not approved for 100% continuous load.